|
[ << Previous | Contents | Next >> ]
In much of the developed world, air conditioning has become a near necessity. In the U.S., more than 90% of newly constructed housing units are centrally air-conditioned [ACHRN, 1999]. Two thirds of all dwelling units in the U.S. have central air conditioning and another one-third have one or more room air conditioners. [Appliance, 1997] [U.S. Census Bureau, 2000] Virtually all-commercial building space in the U.S. is air-conditioned. The rapid population growth of the Sun Belt in the U.S. was facilitated, if not enabled, by the universal use of air conditioning. Acceptance of air conditioning varies throughout the developed world, but in general is increasing rapidly in all but the coolest climates. Use of air conditioning for commercial buildings is growing rapidly, even in cooler climates.
The majority of both the existing installed capacity and new production of air conditioning equipment is unitary equipment. Unitary air conditioning equipment is a broad category of air-to-air air conditioning systems and heat pumps, including:
Note that while ductless split systems, room air conditioners, and PTACs are air to air systems, they are not always classified as "unitary" in published market data. Water source air conditioners and heat pumps are used in approximately 2% of new air conditioner applications [U.S. Census Bureau, 1995]. In the TEWI-3 study, TEWI comparisons were developed for the first three of these types of unitary equipment, in a variety of climatic locations and at several different efficiency levels.
In the present study, the focus is limited to the first two of the above categories of unitary equipment, and energy and LCCP comparisons are presented for a typical residence and a typical small office building in Atlanta, a location whose climate is somewhat warmer than the U.S. average. The prototypical systems that have been analyzed are two of the example systems used in the TEWI-3 study:
For several decades, virtually all of the unitary air conditioning types described above have operated on a reverse Rankine cycle, commonly referred to as the standard vapor compression cycle, using HCFC-22 as the refrigerant. Some unitary air conditioning products are now being produced with one of two HFC blends, R407C or R410A, and with HFC-134a. While the majority of unitary air conditioning in production today still uses HCFC-22 as the refrigerant, in the post-ODS phase-out context of this study the two HFC blends R407C and R410A are the baseline refrigerants. In the Alternative Refrigerant Evaluation Program (AREP), HFC-134a was also evaluated as a replacement for HCFC-22. HFC-134a requires a larger volume flow rate of refrigerant for a given cooling capacity, requiring a larger compressor displacement and larger diameter tubing throughout, increasing the cost. Consequently, limited unitary equipment is likely to be produced in the future with HFC-134a refrigerant, more in large commercial unitary equipment than in smaller capacities.
Alternatives to the vapor compression cycle include:
For the purposes of comparison of the energy consumption of the refrigerant alternatives, the prototypical 3 ton residential systems and the comparable capacity technical alternatives described above have been analyzed for a representative, 1800 sq. ft. residential application in Atlanta. The prototypical 26.4 kW (7.5-ton) commercial rooftop unit has been analyzed for a representative light commercial application in Atlanta. The results have been calculated using the heating and cooling loads calculated in the TEWI-3 study analysis. In the TEWI-3 study, cooling and heating loads and performance were analyzed for several other locations as well, with comparable results.
Tables 6-1 and 6-2 summarize the electric energy consumption of 10.5 kW (3 ton) central air conditioners in Atlanta and 10.5 kW (3 ton) heat pumps in Atlanta, respectively. Note that in the NAECA-efficiency-standards-driven market for this equipment, energy consumption does not vary with refrigerant choice, per se. For example, if the future NAECA minimum efficiency were to be 12 SEER (note that the rulemaking to determine this level is ongoing and the new minimum has not been determined yet), a large portion of the air conditioners and heat pumps manufactured would meet this level without exceeding it by much, absent significant market demand for higher efficiency systems. The inherent efficiency characteristics of each refrigerant alternative will impact the design (and cost) required to provide the required minimum level of performance.
The differences in the inherent efficiency characteristics of the fluorocarbon alternatives are due to differences in thermodynamic and heat transport properties, and system operating pressure. Among R-22, R-407C, and R410A, these differences, and differences in refrigerant prices, can lead to "comparatively small" differences in manufacturing cost. An analysis of these differences is beyond the scope of this project, but it is recognized that even "comparatively small" differences in manufacturing cost can have a meaningful impact on gross and net profit given the highly competitive nature of a market having more than a half dozen strong manufacturers and scores of smaller manufacturers seeking greater market share.
To use propane as the refrigerant, it is assumed that a secondary loop must be used to deliver the cooling and heating capacity to the building interior. The secondary loop consumes parasitic pumping power and adds a heat transfer temperature difference to the overall thermodynamic lift. To overcome the resulting efficiency loss and meet a minimum efficiency level requires significant offsetting design modifications (e.g., larger heat exchangers, more efficient, but higher cost fan motors) to increase the efficiency. The associated costs, along with other costs associated with the safe use of propane will result in a significant (hundreds of U.S. dollars) increase in manufacturing costs and a larger increase in end-user prices.
Results reported by [Hrnjak, 1999] at the International Congress of Refrigeration indicate that it is technically feasible to make a CO2 transcritical cycle air conditioner with a single speed compressor having an SEER of approximately 10 to 11 (based on measuring the steady state EER at the DOE "B" --- 82oF outdoor temperature test point and accounting for the compressor drive motor efficiency and air moving power). However, the EER of a CO2 cycle decreases with increasing outdoor temperature more rapidly than occurs with conventional vapor cycle air conditioners. As a result, at more stringent (e.g., 95oF) outdoor ambient temperatures, a CO2 based air conditioner will be approximately 10% less efficient than a conventional HCFC-22 vapor-compression cycle having a comparable SEER, an issue where peak electric utility loads are a concern. Development of CO2 based air conditioners is still in the early research stage, providing little basis for projecting manufacturing cost vs. efficiency for comparison with conventional alternatives. Qualitatively, higher costs would be expected due to the higher pressure compressor shell requirement, larger and more costly microchannel heat exchangers, and the need for additional components such as an inter cooler. Additionally, there would be costs for developing and implementing an infrastructure capable of servicing carbon dioxide based equipment, to include new tools, service equipment, and training for technicians.
| SEER Level | Refrigerant | Annual Electric Energy kWh |
| 10 | HCFC-22 | 3,380 |
| 12 | HCFC-22
R-407C R-410A Propane/secondary CO2 |
2,817
2,817 2,817 2,817 2,817 |
| 14 | HCFC-22
R-407C R-410A |
2,414
2,414 2,414 |
| Annual Electric Energy Input, kWh | ||||
| EER/HSPF Levels | Refrigerant | Cooling | Heating | Total |
| 10/6.8 | HCFC-22 | 3,380 | 5.120 | 8,500 |
| 12/7.4 | HCFC-22 R-407C R-410A Propane/secondary CO2 |
2,817 2,817 2,817 2,817 2,817 |
4,700 4,700 4,700 4,700 4,700 |
7,520 7,520 7,520 7,520 7,520 |
| 14/8 | HCFC-22 R-407C R-410A | 2,414 2,414 2,414 |
4,350 4,350 4,350 |
6,765 6,765 6,765 |
The annual electric energy consumption of a 7.5 ton commercial rooftop air conditioner in a typical application in Atlanta is summarized in Table 6-3. The general comments, above, on inherent efficiency differences among refrigerants in residential air conditioning equipment are applicable here as well.
| EER Level | Refrigerant | Annual Electric Energy kWh |
| 10 (Current Technology) | HCFC-22 | 12,230 |
| 11 (2005 Technology) | HCFC-22 R-407C R-410A HFC-134a Propane/secondary Carbon Dioxide |
11,455 11,455 11,455 11,455 11,455 11,455 |
The Life Cycle Climate Performance (LCCP, see Section 1.3) for unitary cooling or unitary cooling and heating is made up of the indirect warming associated with the energy consumption summarized above plus the direct warming associated with refrigerant emissions (the warming effect of the refrigerant plus the embodied energy and fugitive emissions associated with manufacturing). The refrigerant charge size and charge loss rates that were assumed in the TEWI-3 study are summarized in Table 6-4. The GWP values are summarized in Table 6-5, which includes both the GWP of the refrigerant and the equivalent GWP of the energy and fugitive emissions associated with manufacturing and transporting the refrigerant.
| Equipment Type | Refrigerant (R22 or R407C) Charge* kg |
Annual Make-Up | End of Life Loss | |
| 2002 | 2005 | |||
| Ducted Residential (3 ton) | 2.8 | 2% | 2% | 15% |
| Single Package Roof top (7.5 ton) | 6.9 | 1% | 1% | 15% |
| Refrigerant | GWP 100 yr. ITH* | Refrigerant Manufacturing | Total |
| R22 | 1500 | 390 | 1890 |
| 407C | 1525 | 13 | 1538 |
| 410A | 1725 | 14 | 1739 |
| HFC-134a | 1300 | 13 | 1313 |
| Propane | 11 | <0.5 | 11 |
| CO2 | 0 | ~1 | 1 |
The LCCP for residential cooling only units in Atlanta is summarized in Table 6-6, for R22, R407C, R410A, propane, and CO2 at several SEER levels. The LCCP for residential heating and cooling is summarized in Table 6-7.
| SEER Level | Refrigerant | Indirect (Energy) Warming kg CO2** |
Direct Warming | LCCP kg CO2 Equivalent | |
| Lifetime Refrigerant Emissions, kg | Warming Impact kg CO2* Equivalent | ||||
| 10 | HCFC-22 | 32,955 | 1.26 | 2381 | 35,340 |
| 12 | HCFC-22 R-407C R-410A Propane CO2 |
27,466 27,466 27,466 27,466 27,466 |
1.26 1.26 1.03 0.6 1 |
2381 1940 1802 6 1 |
29,850 29,400 29,300 27,500 27,500 |
| 14 | HCFC-22 R-407C R-410A |
23,357 23,357 23,357 |
1.26 1.26 1.03 |
2381 1940 1802 |
25,700 25,300 25,150 |
| SEER Level | Refrigerant | Indirect (Energy) Warming kg CO2 |
Direct Warming | LCCP kg CO2 Equivalent | |
| Lifetime Refrigerant Emissions, kg | Warming Impact kg CO2 | ||||
| 10/6.8 | HCFC-22 | 83,090 | 1.26 | 2381 | 85,470 |
| 12/7.4 | HCFC-22 R-407C R-410A Propane CO2 |
73,320 73,320 73,320 73,320 73,320 |
1.26 1.26 1.03 0.6 1 |
2381 1940 1802 6 1 |
75,700 75,260 75,120 73,320 73,320 |
| 14/8 | HCFC-22 R-407C R-410A | 65,960 65,960 65,960 |
1.26 1.26 1.03 |
2381 1940 1802 |
68,340 67,900 67,760 |
Tables 6-6 and 6-7 are based on an efficiency standards-driven scenario, where the energy efficiency and energy consumption are the same, regardless of refrigerant. As a result the two "natural" refrigerant alternatives, CO2 and propane, with their low GWPs, have the lowest LCCP. However, at an SEER equal to a conventional fluorocarbon refrigerant based system, both propane and CO2 based systems are more costly to manufacture, propane due to the fire safety measures that must be included and CO2 due to the higher pressure, more complex system and larger heat exchangers required to achieve a given efficiency level. If this added cost was spent to produce a higher efficiency fluorocarbon refrigerant based unit, lower TEWI might be achieved through the reduced lifetime energy consumption and the associated reduction of energy related CO2 emissions. Work reported by Keller, et. al. [Keller, 1996] and [Keller, 1997] show that this is the case. With a conventional 12 SEER, HCFC-22 system as the baseline, a hypothetical fire-safe propane based system reduced the warming impact by 10%. With the same incremental cost of the propane system applied to a higher efficiency R-410A system, the TEWI was reduced by at least 12%, providing a lower lifetime warming impact for the same investment (without any fire safety uncertainties).
The LCCP for a single package rooftop in Atlanta is summarized in Table 6-8.
| SEER Level | Refrigerant | Indirect (Energy) Warming kg CO2 |
Direct Warming | LCCP kg CO2 | |
| Lifetime Refrigerant Emissions, kg |
Warming Impact kg CO2 Equivalent | ||||
| 10.3 | HCFC-22 | 119,270 | 2.07 | 3,912 | 123,200 |
| 11 | HCFC-22 R-407C R-410A HFC-134a Propane CO2 |
111,682 111,682 111,682 111,682 111,682 111,682 |
2.07 2.07 1.71 2.07 1.1 2 |
3,912 3,185 2,995 2,718 12 2 |
115,600 114,900 114,700 114,400 111,700 111,700 |
The basic observations that can be drawn from the LCCP values in Tables 6-6 through 6-8 are:
With the exception of its high level of flammability, propane appears to be a suitable replacement for R-22 in all respects. Because of the flammability, and the several kg charge size of typical residential unitary equipment, to use propane for residential air conditioning, it is necessary to restrict the propane charge to outdoor equipment, and couple the cooling and heating to the interior with a secondary loop. While this might adequately eliminate the possibility of an explosion occurring within the confined interior space, further fire-safety measures would be needed in the outdoor unit:
All of the measures described above are technically feasible and involve well-known technology. However, they would add significantly to the cost. When Lennox evaluated this option in the early 1990's, they concluded that the necessary fire safety measures would add 30% to the cost of a residential central air conditioning system.
[ << Previous | Contents | Next >> ]
|